← All posts

Bench notes · EV · Safety

Is your power point cooking? Granny chargers and GPO heat

9 Nov 20266 min read

A granny charger running at 2.4 kW draws 10 A, the full rating of a standard Australian 10 A power point (GPO), for 8 to 20+ hours at a stretch. Almost nothing else in the house does that. A kettle pulls 10 A for three minutes; a heater cycles on and off. An EV charge holds the GPO, its plug and its wiring at their limit all night, every night.

That is fine when everything is in good condition. When it isn't, the weak point slowly cooks. The good news is that the warning signs show up as heat long before anything melts, and heat is easy and cheap to measure.

This post explains why GPOs heat up under granny-charger loads, what the warning signs are, and how a sensor that costs about A$30 can watch the outlet for you. The full build is free in the AP Design Labs Free Library.

Why GPOs heat up

A GPO gets hot because current flows through resistance, and the heat goes up with the square of the current:

P = I² × R

At 10 A, every 0.01 Ω of extra resistance makes 1 W of heat at that spot. A healthy plug-to-socket contact is a few milliohms, so it runs barely warm. A worn or loose contact at 0.1 Ω makes 10 W, concentrated in a point the size of a grain of rice and wrapped in plastic. That is roughly a small soldering iron buried inside your power point.

It also feeds itself. Heat oxidises the brass and relaxes the spring tension in the socket contacts. That raises the resistance, which makes more heat. A connection can degrade a little more each night for weeks before anything visibly fails.

CauseWhat goes wrongTypical clue
Worn socket contactsYears of plugging in relax the spring clips, so the pins touch on a smaller areaPlug feels loose or droops
Plug pulled part-way outThe weight of the charger brick or cable levers the plug, so only the pin tips make contactCharger box hanging from the plug
Loose terminal screws behind the faceplateThe wire termination itself becomes the hot spotFaceplate warm around the screws even where the plug is cool
Oxidised or dirty pinsCorrosion film adds resistance; common in damp garages and carportsDull or discoloured pins
Poor-quality plug or socketThin brass and weak clips have less margin at 10 A continuousBudget outlet or a non-original charger lead
Extension leads, double adaptors, power boardsEvery extra joint is another possible hot spot, often with thinner conductorsAnything between the charger and the wall
Worn GPO switchThe switch contacts carry the full 10 A tooHeat on the switch side of the faceplate
Hot surroundingsA sun-facing wall or a 40 °C garage leaves less headroom before parts softenProblems mostly on summer nights
⚠ Your circuit breaker will not save you from this

A bad connection still only draws 10 A, so the breaker sees a normal load and the RCD sees no leakage. Heat is the only symptom, which is why it is worth measuring.

EV owners report exactly this pattern. One SolarQuotes commenter described contacts overheating at a continuous 10 A, partly because the plug was slightly extracting under the weight of the lead. The City of Unley's EV fact sheet also warns that regular charging from a standard power point can heat-damage the socket and plug.

Warning signs to look for

If you see any of these, stop charging from that outlet and have a licensed electrician check it:

The problem with these signs is that they show up late, and usually in the middle of the night when nobody is in the garage. A sensor doesn't sleep.

A simple way to measure it

The AP Design Labs GPO Temperature Monitor uses an ESP32 and two DS18B20 digital temperature sensors, programmed in MicroPython with Thonny. Nothing is opened, wired into, or attached to the mains:

The DS18B20 is a good fit: it reads from −55 °C to +125 °C, is accurate to ±0.5 °C between −10 °C and 85 °C, and several sensors can share one data wire because each has its own 64-bit address.

Why measure the rise rather than just the temperature? A faceplate at 38 °C means nothing on a 36 °C Adelaide night, but a lot on a 12 °C winter night. Comparing against the room removes the weather from the reading.

One honest limitation: the sensor reads the faceplate surface, not the brass contacts inside. The inside will always be hotter than the reading, and it reacts a little slower. That is why the alarm levels below are deliberately conservative.

The GPO temperature monitor in use: granny charger plugged in, DS18B20 probe taped to the outside of the faceplate, ESP32 in its enclosure, and the phone showing WATCH with the GPO 13.5 °C above the room
The sensor stays on the outside of the faceplate; nothing is opened or wired into the GPO. Here the GPO is 13.5 °C above the room, so the monitor shows Watch.

Free library

GPO temperature monitor for EV granny chargers

The full build: parts list, wiring, a safe mounting guide, and the complete MicroPython code for Thonny.

Build it free →

What the readings mean

These are the levels the monitor uses by default. They are AP Design Labs' conservative rules of thumb for a surface reading, not values from an Australian Standard, and you can change them in the code.

Faceplate rise above roomLevelWhat it meansWhat to do
Under 10 °COKNormal for 10 A continuousNothing
10–20 °CWatchWarmer than idealCheck the plug is fully home, nothing is levering it, no adaptors; keep an eye on the trend
20–30 °CWarningSomething is adding resistanceStop using this outlet for charging; book an electrician
Over 30 °C, or faceplate over 60 °CAlarmActive overheatingStop the charge from the car or app, switch off at the GPO, then unplug once safe; don't use it again until inspected
The monitor's phone page at three levels: OK with a 4.6 °C rise, Watch with 13.5 °C, and Alarm with 32.3 °C and the buzzer muted
What you see on your phone: a normal charge (OK), a plug getting warm (Watch), and overheating (Alarm).

The trend matters as much as the number. A GPO that ran 6 °C above the room last month and runs 14 °C above it now is degrading, even though it is still only at Watch. The monitor's web page shows the highest reading since start-up so you can spot this.

Better long-term options

A monitor tells you when there is a problem; it doesn't fix the cause. If you charge from a GPO regularly, talk to a licensed electrician about:

And always: no extension leads, double adaptors or power boards between the charger and the wall.

Safety note

This monitor is an early-warning aid, not a safety device or a substitute for an electrical inspection. Never open a GPO or work on fixed wiring yourself. In Australia that work must be done by a licensed electrician.

Sources

#EV#GrannyCharger#ElectricalSafety#ESP32